RESYS M40R with automatic reclosing (earth leakage protection) M40R relay recloses the system up to six consecutive times after preselected time intervals. If the fault is still present after the sequence of six reclosing attempts, the relay is locked in alarm mode and a manual intervention will be required. Features: Time delay between two reclosings: 7.7 – 15 – 30 – 60 – 120 – 240 second SERIES RESYS M40R CURRENT SETTING I△n 0.03 – 30A TIME DELAY (SECOND) 0 – 10 POWER SUPPLY 115/230 VAC MOUNTING Modular DIN rail (same format as MCB’s) 44mm wide TIME DELAY BETWEEN TWO RECLOSINGS 7.7 – 15 – 30 – 60 – 120 – 240 seconds DESCRIPTION Reclosing earth leakage relay
0.03-30A AUTO RECLOSE E/LEAK REL
Earth leakage protection
ElectroMechanica
4941 3724