TRUE OFF DELAY ON DE-ENERGISATION TIMER (DELAY ON REMOVAL OF SUPPLY).THE ELECTRO 11 PIN PLUG-IN RANGE OF CONTROL AND TIMING DEVICES ARE TO BE INSTALLED INTO A STANDARD 11 PIN BASE MAKING INSTALLATION EASY AND CONVENIENT. THE UNIT PROVIDES DELAYED RELEASE OF RELAY AFTER THE SUPPLY HAS BEEN REMOVED. TIME RANGES FROM 10- 180MIN ARE SUPPLIED WITH INTERNAL BATTERY WHICH HAS TO BE CHARGED FOR 24 HOURS BEFORE IT IS FIRST USED. POWER MUST BE SUPPLIED FOR 30% OF TIME RANGE BEFORE REMOVED TO CHARGE INTERNAL RETAINING CIRCUIT. IN APPLICATIONS WHERE SUPPLY VOLTAGE IS PRESENT THE PULSE CONTROLLED INTERVAL TIMER (T2M OR T1I/P) SHOULD BE USED..FEATURES:. OUTPUT 5A DPDT OSCILLATOR CONTROL TIME CIRCUIT REPEATABLE DEVIATION: < 1% LED INDICATION FOR POWER SUPPLY ON POTENTIOMETER ADJUSTABLE TIME SETTING TIME RANGE 10- 180MINUTE WITH BATTERY TIME RANGE 3 - 360 SECOND WITHOUT BATTERY FOR PULSES SHORTER THEN 30S + 30%, PT11/PT13 SHOULD BE USED .TIME RANGE 10MIN, 30MIN, 60MIN,180MIN .DESCRIPTION TRUE OFF DELAY ON DE-ENERGISATION TIMER WITH BATTERY .CONTACT 10A SPDT .RATED VOLTAGE 250V .MECHANICAL LIFE 10X106 CYCLES .PROTECTION INDEX IP IP 20 .OPERATING TEMPERATURE -10 TO + 50B0C .STORAGE TEMPERATURE -50 TO + 85B0C .DIMENSIONS (MM) (H) 92 X (W) 36 X (D) 64 .
Request a Quote to Recieve Discount
OFF DELAY TIMER, 180 MIN, 230VAC
Request a Quote to Recieve Discount
SKU: T2D/B180M230A
Category Timers and Control Relays
R0.00 Excluding Vat