True off delay on de-energisation timer (delay on removal of supply) The Electro 11 pin plug-in range of control and timing devices are to be installed into a standard 11 pin base making installation easy and convenient. The unit provides delayed release of relay after the supply has been removed. Time ranges from 10- 180min are supplied with internal battery which has to be charged for 24 hours before it is first used. Power must be supplied for 30% of time range before removed to charge internal retaining circuit. In applications where supply voltage is present the pulse controlled interval timer (T2M or T1I/P) should be used. Features: Output 5A DPDT Oscillator control time circuit Repeatable deviation: 1% LED indication for power supply ON Potentiometer adjustable time setting Time range 10- 180minute with battery Time range 3 – 360 second without battery For pulses shorter then 30s + 30%, PT11/PT13 should be used TIME RANGE 3s,10s, 30s, 60s, 180s, 380s DESCRIPTION True off delay on de-energisation timer CONTACT 10A SPDT RATED VOLTAGE 250V MECHANICAL LIFE 10×106 cycles PROTECTION INDEX IP IP 20 OPERATING TEMPERATURE -10 to + 50°C STORAGE TEMPERATURE -50 to + 85°C DIMENSIONS (MM) (H) 92 x (W) 36 x (D) 64